The Honeywell E3Point commercial-grade toxic and combustible gas monitoring system allows operations to run more intelligently and efficiently.
E3Point commercial gas monitor is capable of detecting the widest range of toxic and combustible gases found in commercial building spaces and outbuildings, including CO, NO2, O2, H2, H2S, CH4 and C3H8. It can be used as a standalone unit with single or dual-gas detection (i.e. using a remote sensor) or deployed as a networkable device (interoperable with BACnet, Modbus or other Building Automation System); E3Point also functions with existing controller-based gas monitoring systems and wired-wireless gas monitoring system components.
E3Point commercial gas monitor utilizes Demand Control Ventilation—through relays, Building Automation System (BAS) or Controllers—to increase energy savings, extend fan life and align with green building best practices. In its network configuration, E3Point also optimizes HVAC, fire/smoke, surveillance and other building systems performance.
BrochureIntelligent product design reduces the unit’s cost of ownership while increasing flexibility of application. Smart sensors are pre-calibrated, auto-configure upon set-up and operate continuously on patented Reflex© technology which continuously monitors sensor cell condition and alerts user to fault status. The plug-n-play sensor cartridge, user-friendly menu and wiring options simplify installation and maintenance, and reduce the cost of gas monitoring over the life of the unit.
The Honeywell E3Point commercial-grade toxic and combustible gas monitoring system allows operations to run more intelligently and efficiently.
E3Point commercial gas monitor is capable of detecting the widest range of toxic and combustible gases found in commercial building spaces and outbuildings, including CO, NO2, O2, H2, H2S, CH4 and C3H8. It can be used as a standalone unit with single or dual-gas detection (i.e. using a remote sensor) or deployed as a networkable device (interoperable with BACnet, Modbus or other Building Automation System); E3Point also functions with existing controller-based gas monitoring systems and wired-wireless gas monitoring system components.
E3Point commercial gas monitor utilizes Demand Control Ventilation—through relays, Building Automation System (BAS) or Controllers—to increase energy savings, extend fan life and align with green building best practices. In its network configuration, E3Point also optimizes HVAC, fire/smoke, surveillance and other building systems performance.
BrochureIntelligent product design reduces the unit’s cost of ownership while increasing flexibility of application. Smart sensors are pre-calibrated, auto-configure upon set-up and operate continuously on patented Reflex© technology which continuously monitors sensor cell condition and alerts user to fault status. The plug-n-play sensor cartridge, user-friendly menu and wiring options simplify installation and maintenance, and reduce the cost of gas monitoring over the life of the unit.
Cost Effective
• Saves energy through Demand Control Ventilation (DCV)
• Simplifies installation/maintenance through plug-n-play sensor
• Remote sensor option provides dual gas monitoring (standalone version only)
• Optimizes BAS, fire, ventilation and other security systems
Versatile Communications
• Works through BAS to improve fault diagnostics and collect data on gas concentration levels, sensor condition, etc.
• Couple with 301C to log data and daisy-chain up to 96 E3Point units
Advanced Sensing Technology
• Detects CO, NO2, O2, H2, H2S, CH4, C3H8
• Advanced electrochemical (for toxic gases)and catalytic bead (for combustible gases) sensor performance
• Uses patented Reflex® and smart cartridge technologies
Electrical Certifications
• US (ANSI/UL 61010-1)
• Canada (CSA C22.2 No. 61010-1)
General Specifications
Uses Wall or duct-mounted, BAS or controller networkable gas detector for monitoring carbon monoxide (CO),
nitrogen dioxide (NO2), hydrogen sulfide (H2S), oxygen (O2), methane (CH4), hydrogen (H2) and propane (C3H8).
Size 20.56 x 14.90 x 6.72cm (8.09 x 5.87 x 2.65”) (H x W x D)
Power Requirement 24 Vac nominal (17-27Vac), 50/60 Hz, 0.35 A; 24 Vdc nominal (20-38Vdc)
Relay Output 1 DPDT relay, 5A @ 250Vac; 5A @ 30Vdc
Communications RS485 Modbus; BACnet MS-TP master
Operating Environment Commercial, Indoor, Extreme Temperature Environments
Operating Temperature H2S, NO2, O2, CH4, H2, C3H8: -40 to 50ºC (-40 to 122ºF)
CO: -20 to 50ºC (-4 to 122ºF)
Response Time T90 < 50 seconds
With ECLAB T90 < 240 seconds
Display 8 character, 2 line backlit LCD
Visual Indicators Green LED: Power
Amber LED 1: Alarm/Fault
Amber LED 2: Alarm/Fault
Audible Alarm >85 dBA at 3 m (10 ft)
Accuracy ± 3% of full scale @ 25 C
Gases Detected, Detection Ranges and Alarm Levels
Gas Resolution Range Alarm A Alarm B Alarm C
CO (Carbon monoxide) 1 ppm 0-250 ppm 25 ppm 100 ppm 225 ppm
H2S (Hydrogen sulfide) 0.1 ppm 0-50 ppm 10 ppm 15 ppm 20 ppms
NO2 (Nitrogen dioxide) 0.1 ppm 0-10 ppm 0.7 ppm 2 ppm 9 ppm
O2 (Oxygen) 0.1% vol. 0-25% vol. 19.5% vol. 22% vol. 22.5% vol.
H2 (Hydrogen) 0.5% LEL 0-100% LEL 25% LEL 50% LEL 90% LEL
CH4 (Methane) 0.5% LEL 0-100% LEL 25% LEL 50% LEL 90% LEL
C3H8 (Propane) 0.5% LEL 0-100% LEL 25% LEL 50% LEL 90% LEL
Enclosure
Polycarbonate
Certification
CSA C22.2 No. 61010-1, UL 61010-1; FCC part 15; ICES-003 issue 4; ISO 9001-2008
Honeywell Analytics - Honeywell Toxic/Combusitble Commercial Gas Monitor E3Point | ||
---|---|---|
Order # | Model # | Description |
1309A0042 | E3SA | E³Point without sensor, wall mount, analog, 24 Vac/Vdc |
1309A0043 | E3SAH | E³Point without sensor, wall mount, analog, 120 Vac |
1309A0047 | E3SM | E³Point without sensor, wall mount, Modbus/BACnet, 24 Vac/Vdc |
1309A0060 | E3SRMCO | E³Point remote sensor, carbon monoxide (CO) |
1309A0057 | E3SRMNO2 | E³Point remote sensor, nitrogen dioxide (NO2) |
1309A0058 | E3SRMH2S | E³Point remote sensor, hydrogen sulfide (H2S) |
1309A0059 | E3SRMH2 | E³Point remote sensor, hydrogen (H2) |
1309A0056 | E3SRMO2 | E³Point remote sensor, oxygen (O2) |
1309A0061 | E3SRMM | E³Point remote sensor, methane (CH4) |
1309A0062 | E3SRMP | E³Point remote sensor, propane (C3H8) |
1309A0049 | E3DA | E³Point without sensor, duct mount, analog, 24 Vac/Vdc |
1309A0051 | E3DM | E³Point without sensor, duct mount, Modbus/BACnet 24 Vac/Vdc |
1309A0038 | E3SCO | Carbon monoxide (CO); -20° to 50°C (-4° to 122°F) |
1309A0037 | E3NO2 | Nitrogen dioxide (NO2); -40° to 50°C (-40° to 122°F) |
1309A0035 | E3H2S | Hydrogen sulfide (H2S); -40° to 50°C (-40° to 122°F) |
1309A0039 | E3H2 | Hydrogen (H2); -40° to 50°C (-40° to 122°F) |
1309A0036 | E302 | Oxygen (O2); -40° to 50°C (-40° to 122°F) |
1309A0040 | E3M | Methane (CH4); -40° to 50°C (-40° to 122°F) |
1309A0041 | E3P | Propane (C3H8); -40° to 50°C (-40° to 122°F) |
1309-0071 | E3PT-CAGE | Protective wire guard for E³Point |
1309K0001 | E3T-PK | E³Point tamper-proof kit |
1309K0003 | ECLAB | Splash guard enclosure |
TEST-1A | TEST-1A | Bump test kit; includes balloon adapter and quad gas cylinder: H2S (40 ppm), CO (200 ppm), CH4 (2.5%), O2 (10%) |
Honeywell Analytics
For nearly 50 years, Honeywell Analytics has been protecting people who put their lives on the line every day. It takes a special level of drive and dedication to work in hostile environments, and we believe your workers deserve the same kind of commitment from us when it comes to securing their health and safety. Right from the start, our founders were determined to find better ways to design, build and manufacture reliable gas detection solutions. Through advanced technology and pure industry know-how, Honeywell Analytics continues to improve and evolve our products. Today, we’re proud to partner with customers worldwide who share our vision of vigilance and rely on us to help them protect what matters most. From custom-designed solutions to unmatched training and support, Honeywell Analytics is simply the smartest choice when you demand the best in safety.
Toxic or combustible gas monitor for commercial buildings – E3Point from Honeywell Analytics