Honeywell Q179A Q179B Pilot Burners

Assemblies use the flame rectification principle to prove the flame.

Honeywell Q179A Q179B Pilot Burners product thumbnail
Get in Touch
button-arrow-red Back

Q179A,B Gas Pilot Burner Assemblies use the flame rectification principle to prove the flame. Q179A,B are used in conjunction with a suitable electronic flame safeguard control on industrial or commercial gas and gas pilot ignited oil burners.

• Q179A is a gas pilot assembly with a flame electrode (rod) and ignition electrode, making it suitable for applications requiring an interrupted or intermittent electrically ignited gas pilot burner.

• Q179A1183 is an “I” port burner with an ignition electrode (spark) only.

• Q179B has only the flame electrode and is suitable for use in continuous pilot applications.

 

Download Product Specifications

• Primary aerated type burner is equipped with stainless steel fins that provide the proper flame rod area to ground area ratio for maximum flame signal and flame stabilization. • Stainless steel electrode(s) are mounted in ceramic insulators, which permit electrode adjustment.

Application: For Intermittent or Interrupted Ignition

Dimensions (in.): 4 5/8 in. high x 1 11/16 in. wide x 3 in. deep

Dimensions (mm): 118 mm high x 43 mm wide x 76 mm deep

Includes: Flame electrode and ignition electrode

Used With: Q624 or other suitable ignition transformer.

Mounting: side or end mount

Approvals: Underwriters Laboratories Inc.Listed: File No. MP268, Guide No. MCCZ

Approvals: CSACertified: File No. LR1620, Guide No. 140-A-2

Approvals: Factory MutualApproved: Report No. 22961

Type of Gas: Natural gas; Gas consumption–2.0 cfh (0.06 m3/hr)

Aeration: Primary

Compression Fitting Size: 1/4 in. compression coupling,6.4 mm compression coupling

Orifice: 0.025 in. dia. (0.635 mm dia.)

Wiring Terminal Type: Rajah

Tip Style: 45 degree right hand

Q179A1035/U

Flame rectifier pilot for intermittent or interrupted ignition

Q179A1050/U

Flame Rectif.Pilot w.028 in.dia. Orifice

Q179A1076/U

Flame rectifier pilot for interrupted or intermittent ignition

Q179A1092/U

Flame rectifier pilot with a 0.028 in. diameter orifice

Q179A1118/U

Flame rectifier pilot for intermittent or interrupted ignition

Q179A1126/U

Flame Rectif.Pilot w.025 in.dia. Orifice

Q179A1183/U

Flame rectifier pilot includes 0.025 in. diameter orifice

Q179B1042/U

Flame rectifier pilot has .025 in. diameter orifice and T tip style

Q179B1067/U

Flame Rectif.Pilot w.028 in.dia. Orifice

Q179B1109/U

Flame rectifier pilot includes .025 in. diameter orifice

100204B/U

Natural Gas Venturi Mixing Tube-C7005A,B

101738/U

Insulator for Flame rod or Igniter

101738A/U

Ignition assembly includes electrode, bracket and Rajah connector

101738B/U

Flame Rod Assembly

101739/U

Ignition Electrode, 4 in., Kanthal

101743/U

Mounting Bracket

103534/U

Kanthal flame electrode – C7005A, C7005B

104312/U

Rajah Cnctr for Flame Electrode-Q179A, B

131065/U

Adapts Q340 Thermal Couple to Q179B

133451A/U

T Port or LH 90 degree Flame Rod & Insul

388146AF/U

Natural Gas spud orifice, .024 in. dia.

388146KD/U

.016 inch diameter LP Gas spud orifice for Q179C, Q179D

395390-13/U

LP Gas Orifice .013″ dia. for Q179A, B

395390-28/U

Natural Gas Orifice .028″ dia. -Q179A, B

R1061012/U

Ignition cable or Flame Rod Cable

R1298020/U

Cable Flame Rod Lead. Rated at 400 F

101741/0020/U

Rajah Connector w plug end-C7005A/C7005B

101742/0021/U

Electrode Mounting Clip-C7005A or C7005B

37356/520/U

Rajah connector for ignition electrodes

Honeywell Environmental & Energy Solutions

Honeywell is an industry leader in manufacturing a comprehensive line of combustion equipment to meet critical heating requirements of virtually every industrial process. Honeywell burner management systems are designed in a variety of configurations to heat air streams, liquids, ovens and furnaces with outstanding efficiency, reliability and performance. Honeywell also offers combustion control valves, viz. Shut-Off valves and Control valves. These present many operational advantages to help prevent leakage and are engineered and tested for life cycles of 1,000,000 closures. This type of performance leadership along with excellent expertise and customer focused approach has made Honeywell a highly trusted and sought after name in combustion products worldwide –serving a multitude of industries in a multitude of applications. SIL3 Capable and CSA B149.3 certified burner management system solutions include state of the art flame controls, fuel air ratio controls, pressure switches, gas solenoid valves, mod motors and associated accessories are stocked by MicroWatt and backed by our experienced technical staff and engineering group.

Honeywell Commercial/Industrial Combustion

Have any questions?

We'd love to help

Get in touch

Call Us Toll Free Across Canada!

1.888.388.1592

Corporate Headquarters

101-11127 15 Street NE,
Calgary, AB Canada T3K 2M4
1.403.250.1594
edge-footer-top-blue footer-tower
  • LinkedIn
  • YouTube
View all Accreditations
  • COR
  • ISN
  • Avetta
A sillouette of an oil and gas plant.

© 2025 MicroWatt Controls | Website by True Market