MANUFACTURED BY:

  • Overview
  • Features
  • Additional Information
  • Features Detail
  • Specifications
  • Manufacturer
  • The Honeywell Analytic’s Series 3000 MkII and MkIII Toxic Transmitter with Sensor provides comprehensive monitoring of toxic and Oxygen gas hazards in potentially explosive atmospheres, both in and out of doors.

    The Series 3000 is available in two versions and offer excellent versatility. The MkII is contained in a flameproof housing, has an intrinsically safe sensor connection and is for use in predominantly Zone 1 applications. However, with the use of the optional remote mounting kit the sensor of the MkII can be mounted in a Zone 0 environment. The MkIII is for use with a separate suitable IS barrier allowing the complete transmitter to be used in Zone 0 applications.

    The Honeywell Analytic’s Series 3000 MkII and MkIII Toxic Transmitter with Sensor are low powered gas detectors that all feature a loop powered 4-20 mA connection, making them ideal for both new and retrofit installations. Users can configure the detector through the use of the easy to read LCD and intuitive interface while fault diagnostic software and a programmable calibration period greatly simplify maintenance procedures.

    Brochure
    MkII Specifications
    MkII Manual

  • • Loop powered, 2-wire gas detector
    • Reliable detection, reduced installation costs
    • Reduced commissioning costs
    • Proven electrochemical sensing technology
    • Uses Surecell™ electrochemical cells, ideal for hot and humid environments
    • Long life sensing elements (typical >2 years)
    • Patented ‘Reflex’ sensing element verification diagnostics
    • Universal mounting bracket included supplied as standard
    • Flameproof transmitter allows field wiring to be run along with other non IS instruments
    • Plug-in sensor removes wiring
  • Series 3000 MkII and MkIII are intrinsically safe smart sensors are supplied pre-configured and can be ‘hot swapped’ without having to remove power to the detector, saving time and money during commissioning and routine servicing. A remote sensor mounting kit is available that allows the sensor to be mounted up to 15m (50ft) from the transmitter, making it ideal for operation in areas that are difficult to access.

    Series 3000 is supplied with all necessary accessories for easy installation. The detector can be wall mounted using the integral mounting lugs or pipe mounted (horizontal or vertical) using the optional pipe mounting kit. Electrical installation is made using the 2 x M20 cable entries (ATEX/IECEx version) or 2 x ¾”NPT conduit entries (UL/c-UL versions). A suitable blanking plug is also supplied to seal any unused entries. A weatherproof cap is included for use in the harshest outdoor conditions.

  • Reliable detection

    • Proven electrochemical sensing technology
    • Uses Surecell™ electrochemical cells, ideal for hot and humid environments
    • Long life sensing elements (typical >2 years)
    • Patented ‘Reflex’ sensing element verification diagnostics

    Reduced installation costs

    • Integral surface mounting lugs
    • Optional horizontal or vertical pipe mounting bracket
    • Flameproof transmitter allows field wiring to be run along with other non-IS instruments
    • Plug-in sensor removes wiring
    • Can be retrofitted in place of Series 2000

    Reduced commissioning costs

    • Sensor recognition feature auto configures transmitter
    • Non-intrusive configuration
    • Plug and play factory configured sensors

    Reduced maintenance costs

    • IS sensor connection permits hot swap, reducing down time
    • User programmable calibration frequency
    • Integral fault diagnostic software
    • Menu / icon driven calibration procedure

  • MKII Specifications

    Electrical

    Connections and power: 2-wire loop powered; 17Vdc (+/-10%) to 24Vdc (max) operation; 22mA max. over range
    Recommended cable: 2-wire with shield (90% coverage) or conduit; 0.5mm2 (20AWG) to 2.0mm2 (14AWG)
    Signal: 0-100%FSD 4-20mA; Fault = 3mA; Calibration due selectable off or 3mA Max. over range 22mA; Inhibit (toxic sensors) = Selectable 3mA or 4mA Inhibit; (Oxygen sensors) = Selectable 3mA or 17.4mA

    Construction

    Material: Transmitter: Epoxy painted aluminum allow LM25 or 316 stainless steel Sensor: 316 stainless steel with PTFE filter
    Maximum Dimensions: 6.4 x 7.9 x 3.9 inches; 164 x 201 x 99mm
    Weight: Aluminum alloy: 3.75 lbs./1.79 kg; stainless steel: 8.16 lbs./3.7 kg

    Environmental

    IP rating: IP66 (EN60529), NEMA 4X
    Operating humidity: Continuous 20-90% RH (non-condensing); Intermittent 0-99% RH (non-condensing)
    Operating pressure: 90-110kPa
    Storage conditions: 59°F to 86°F (15°C to 30°C) | 30-70%RH (non-condensing)
    Certification:
    UL/c-UL Class I, Div 1 & 2, Groups B, C & D; Class II, Div 1, Groups E, F, G; Class II, Div 2,
    Groups F & G, Class I Zone 1, Group 2B + H2 Hazardous Locations
    ATEX: II 2 (1) G Ex d [ia] IIB+H2 T4 (Tamb -4°F to +131°F/-20°C to +55°C)
    IECEx Ex d [ia] IIB + H2 T4

    MKIII Specifications

    Electrical

    Connections and power: 2-wire loop powered; 10Vdc (+/-10%) to 30Vdc (max) operation; 22mA max. over range
    Recommended cable: 2-wire with shield (90% coverage) or conduit; 0.5mm2 (20AWG) to 2.0mm2 (14AWG)
    Signal: 0-100%FSD 4-20mA; Fault = 3mA; Calibration due selectable off or 3mA Max. over range 22mA; Inhibit (toxic sensors) = Selectable 3mA or 4mA Inhibit; (Oxygen sensors) = Selectable 3mA or 17.4mA

    Construction

    Material: Transmitter: Epoxy painted aluminum allow LM25 or 316 stainless steel Sensor: 316 stainless steel with PTFE filter
    Maximum Dimensions: 6.4 x 7.9 x 3.9 inches; 164 x 201 x 99mm
    Weight: Aluminum alloy: 3.75 lbs./1.79 kg; stainless steel: 8.16 lbs./3.7 kg

    Environmental

    IP rating: IP66 (EN60529), NEMA 4X
    Operating Temperature:  ATEX/IECEX: -40°C to +55°C  UL/cUL: -40°C to +55°C
    Operating humidity: Continuous 20-90% RH (non-condensing); Intermittent 0-99% RH (non-condensing)
    Operating pressure: 90-110kPa
    Storage conditions: Transmitter:-40°C to +55°C (-40°F to +131°F) 30-70% RH (non condensing)
    Certification: Transmitter: ATEX:  II 1 (1) GD Ex ia IIC T4 Ga  Ex ia IIIC T135oC Da
    Remote Sensor Accessory: ATEX  II 1 GD Ex ia IIC T4 Ga  Ex ia IIIC T135oC Da Transmitter: IECEx UL 11.0010X Ex ia IIC T4 Ga  Ex ia IIIC T135oC Da
    Remote Sensor Accessory: IECEx: Ex ia IIC T4 Ga  Ex ia IIIC T135oC Da

    MKIII Toxic and Oxygen Smart Sensors:
    XNXXSA2SS – Ammonia (NH3) 0-1,000ppm (200 to 1,000ppm, 50ppm)
    XNXXSA1SS – Ammonia (NH3) 0-200ppm (50 to 200ppm, 50ppm)
    XNXXSC1SS – Carbon monoxide (CO) 0-300ppm (100 to 999ppm, 100ppm)
    XNXXSL1SS – Chlorine (Cl2) 0-5.0ppm (5.0 to 20.0ppm, 5.0ppm)
    S3KX1SS – Chlorine dioxide (ClO2) 0-1.00ppm
    XNXXSG1SS – Hydrogen (H2) 0-1,000ppm
    XNXXSG2SS – Hydrogen (H2) 0-10,000ppm
    S3KXSR1SS – Hydrogen chloride (HCl) 0-10ppm (10.0 to 20.0ppm, 1.0ppm)
    S3KXSY1SS – Hydrogen cyanide (HCN) 0-20.0ppm
    XNXXSR1SS – Hydrogen chloride (HCl) 0-10ppm (10.0 to 20.0ppm, 1.0ppm)
    XNXXSF1SS – Hydrogen fluoride (HF) 0-12.0ppm
    XNXXSH2SS – Hydrogen sulfide (H2S) 0-100ppm (50 to 500ppm, 10ppm)
    XNXXSH1SS – Hydrogen sulfide (H2S) 0-15ppm (10 to 50ppm, 1ppm)
    XNXXSN1SS – Nitrogen dioxide (NO2) 0-10.0ppm (5.0 to 50.0ppm, 5.0ppm)
    XNXXSM1SS – Nitrogen monoxide (NO) 0-100ppm
    XNXXSO1SS – Oxygen (O2) 0-25 pct. vol
    XNXXSP1SS – Phosphine (PH3) 0-1.2ppm
    XNXXSS1SS – Sulfur dioxide (SO2) 0-15.0ppm (5.0 to 20.0ppm, 5.0ppm)

  • Honeywell Analytics

    For nearly 50 years, Honeywell Analytics has been protecting people who put their lives on the line every day. It takes a special level of drive and dedication to work in hostile environments, and we believe your workers deserve the same kind of commitment from us when it comes to securing their health and safety. Right from the start, our founders were determined to find better ways to design, build and manufacture reliable gas detection solutions. Through advanced technology and pure industry know-how, Honeywell Analytics continues to improve and evolve our products. Today, we’re proud to partner with customers worldwide who share our vision of vigilance and rely on us to help them protect what matters most. From custom-designed solutions to unmatched training and support, Honeywell Analytics is simply the smartest choice when you demand the best in safety.

    Oxygen and Toxic Gas Detector – Series 3000 Mkll & MkIII Transmitter with Sensor – Honeywell Analytics